The Schneider Electric A9N61526 is a genuine Acti9 C60H-DC direct-current miniature circuit breaker — 2-pole, 6A, C curve, rated up to 500V DC. It is designed for the DC side of solar and battery-storage systems, protecting battery-bank circuits, hybrid and residential or commercial solar DC, telecom DC power and DC distribution boards against overload and short circuit. Unlike a standard AC MCB, it is built with DC-rated magnetic arc chutes to safely interrupt direct-current faults. Electrical Junction supplies it as genuine Schneider stock with technical support and SASO / SABER documentation for the Saudi and GCC market.
The A9N61526 protects individual DC circuits wherever a reliable, genuine DC-rated breaker up to 500V DC is required — with solar and battery storage as the primary use case. At 6A it suits smaller DC sub-circuits and control feeds.
A direct-current circuit must be protected by a DC-rated breaker. Direct current does not cross zero the way AC does, so a DC fault arc is harder to extinguish and can sustain across the breaker contacts. The Acti9 C60H-DC is built with DC-rated magnetic arc chutes and a defined pole-series wiring arrangement to interrupt DC faults safely — a standard AC MCB used on a DC circuit can fail to clear the fault and is unsafe. This is why solar and battery installations specify DC-rated devices like the A9N61526 on the DC side.
The A9N61526 (C60H-DC) is a general-purpose DC MCB rated up to 500V DC, ideal for battery-bank circuits, DC distribution and lower-voltage solar and hybrid DC. For high-voltage photovoltaic strings above 500V DC — typically 800 to 1000V on utility and large commercial arrays — Schneider offers the dedicated C60PV-DC range instead. Choosing the correct one matters: our engineering team can confirm the right device for your system's maximum DC voltage, including cold-temperature correction for PV strings.
Saudi Arabia's solar and battery-storage rollout is racing ahead of component supply, and installers regularly face long lead times on balance-of-plant parts. We hold genuine Schneider DC breakers in our Dubai hub and ship to Saudi Arabia by road, typically arriving on site in about 7-10 days — with SASO / SABER conformity documentation prepared in advance so your shipment clears customs without delay. Our engineer Ahamed reviews DC voltage, current and application before dispatch, so you receive a correctly-rated genuine Schneider device rather than a mismatched or grey-market part. For pricing, stock confirmation and a formal quote, message us on WhatsApp at +971 55 414 9418.
Can I use the Schneider A9N61526 on the DC side of a solar or battery system?
Yes, within its voltage limit. The A9N61526 (Acti9 C60H-DC) is rated up to 500V DC, which suits battery-bank DC circuits, hybrid and residential or commercial solar systems, and DC distribution operating at or below 500V DC. For high-voltage photovoltaic strings above 500V DC (typically 800-1000V), use Schneider's dedicated C60PV-DC range instead. Always compare the breaker's DC rating against your system's maximum DC voltage, including cold-temperature correction for PV.
What is the DC voltage and breaking capacity of the A9N61526?
The A9N61526 has a rated operational voltage up to 500V DC. Its ultimate breaking capacity (Icu) to IEC/EN 60947-2 is 20kA at 220-250V DC, 10kA at 440V DC and 6kA at 500V DC. The two poles are connected in series to achieve the higher DC voltage rating.
Why can't I use a standard AC MCB on a DC circuit?
A DC circuit needs a DC-rated breaker because direct current does not cross zero the way AC does, so a DC fault arc is harder to extinguish and can sustain across the contacts. The C60H-DC uses DC-rated magnetic arc chutes and defined pole-series wiring to interrupt DC faults safely; a standard AC MCB used on DC can fail to clear the fault.
Is the A9N61526 the same as the C60PV-DC?
No. The A9N61526 is an Acti9 C60H-DC, a general-purpose DC MCB rated up to 500V DC for battery, DC distribution and lower-voltage solar circuits. The C60PV-DC is a separate range designed specifically for high-voltage photovoltaic strings up to around 1000V DC. Confirm which your application needs before ordering, or our engineer can advise.
What amperage ratings does the Acti9 C60H-DC range come in?
The 2-pole Acti9 C60H-DC C-curve range runs from 0.5A up to 63A. Common ratings include the A9N61526 at 6A, A9N61531 at 16A and A9N61532 at 20A. All share the same 500V DC rating and breaking capacity, so you select the amperage that matches your DC circuit's design current. We stock a range of ratings and can advise the correct one.
Do you deliver the A9N61526 to Saudi Arabia with SASO documentation?
Yes. Electrical Junction holds genuine Schneider A9N61526 stock in our Dubai hub and ships to Saudi Arabia by road, typically arriving on site in about 7-10 days, with SASO and SABER conformity documentation prepared for smooth customs clearance into the Kingdom.
| SKU | MAS03524A9N61526 |
|---|---|
| Weight (kg) | 0.256000 |
| Manufacturer | Schneider Electric |
| Network Type | AC/DC |
| Number Of Poles | 2P |
| Voltage (volt AC) | 500 V DC |
| Standard | EN 60947-2 |
| Rated Frequency | 50/60 Hz |
| Model Number | A9N61526 |
| RATED AMPERE (A) | 6 |
| Electrical Durability | 20000 cycles |
| Circuit Breaker Type | Miniature Circuit Breakers |