The Schneider Electric A9R12491 is a 4-pole, 100A Acti 9 iID residual current circuit breaker (RCCB) with 100mA Type AC residual-current sensitivity. It provides voltage-independent earth-leakage protection for three-phase-and-neutral distribution boards, guarding against indirect-contact shock and earth-fault fire risk in commercial and industrial installations. It is compliant with EN/IEC 61008-1 and mounts on standard DIN rail.
The A9R12491 is used as a group or incoming residual-current device in three-phase distribution boards where earth-leakage protection is required. At 100mA sensitivity it is typically applied for fire protection and indirect-contact protection, or as an upstream device providing discrimination above 30mA final-circuit RCDs.
No — the A9R12491 is a 100mA device, intended for fire protection and indirect-contact protection, not additional protection on socket circuits. IEC guidance calls for a 30mA RCD for additional protection on final socket circuits. For that, use the 30mA version, Schneider A9R11491.
Type AC (this unit) trips on sinusoidal AC residual currents only. Loads that draw pulsating or smooth DC leakage — variable-speed drives, EV chargers, and some electronic power supplies — can blind a Type AC device, so those installations require a Type A or higher RCD (for example the Type A A9R21491).
No. An RCCB provides residual (earth-leakage) protection only. It must be protected against overload and short circuit by upstream MCBs or an MCCB. Its 10 kA conditional short-circuit rating is only valid when backed by a correctly rated upstream protective device.
They are the same 4-pole, 100A, Type AC Acti 9 iID frame with different earth-leakage sensitivity: A9R11491 is 30mA, A9R12491 (this unit) is 100mA, and A9R14491 is 300mA. Choose the sensitivity to match the protection function — 30mA for additional/shock protection, 100mA/300mA for fire protection and discrimination.
The 4P version is for three-phase-plus-neutral (TP&N) installations. For single-phase (line and neutral) circuits, use the 2-pole Acti 9 iID RCCB of the matching current and sensitivity instead.
| SKU | MAS03539A9R12491 |
|---|---|
| Weight (kg) | 0.370000 |
| Manufacturer | Schneider Electric |
| Network Type | AC |
| Number Of Poles | 4P |
| Voltage (volt AC) | 380...415 V AC 50/60 Hz |
| Standard | EN/IEC 61008-1 |
| Rated Frequency | 50/60 Hz |
| Model Number | A9R12491 |
| Mechanical Durability | 20000 cycles |
| RATED AMPERE (A) | 100 |
| Electrical Durability | AC-1: 10000 cycles |
| Circuit Breaker Type | RCCB |